Universal compatibility with digital sensors: pH/ORP, conductivity/TDS, dissolved oxygen, turbidity, MLSS, and disinfectant sensors.
Isolated current output ensures high noise immunity and reliable signal transmission.
Isolated RS485 communication with Modbus-RTU protocol for stable data exchange.
High/low alarm relay outputs.
Audible and visual alarm function.
LCD backlight on/off control, adaptable to different ambient light conditions.
| Parameter | Specification |
|---|---|
| Measuring Range | pH: 0–14 pHORP: -2000–2000 mVDissolved Oxygen: 0–20 mg/LConductivity: 0–20000 µS/cmTDS: 0–10000 mg/LTurbidity: 0–4000 NTUMLSS: 0–30000 mg/LDisinfectants (Free Cl₂/ClO₂/O₃/Total Cl₂): 0–20 mg/LNote: Actual range depends on the connected sensor. |
| Display | 2.8" monochrome LCD, 128×64 resolution |
| Dimensions | 100 × 100 × 150 mm |
| Panel Cutout | 92.5 × 92.5 mm |
| Supported Parameters | pH / ORP / Conductivity / TDS / Dissolved Oxygen / Turbidity / MLSS / Disinfectants |
| Sensor Input Accuracy | Refer to the connected sensor’s specifications |
| Repeatability | Refer to the connected sensor’s specifications |
| Current Output | Isolated 4–20 mA, range configurable; Load ≤500 Ω; Accuracy ±0.2% FS |
| RS485 Output | Isolated, Modbus-RTU protocol |
| Alarms | 2-channel relay (NO/NC), rating AC 250 V / 3 A |
| Power Distribution Output | 12 V DC / 125 mA |
| Ambient Humidity | 10–85% RH (non-condensing) |
| Power Supply | AC: 100–240 V ACDC: 24 V DC (optional) |
| Power Consumption | ≤6 W |
| Cable Entries | 1 × M12×1.5 gland2 × M16×1.5 glands |
| Operating Temperature | 0–60 ℃ |
| Storage Conditions | Temperature: -15–65 ℃Humidity: 5–95% RH (non-condensing)Altitude: <2000 m |